16.2 HYDRAULIC POWER UNIT: TO MONITOR MINIMUM FLUID LEVEL
WITH ADVANCE WARNING AND MINIMUM TEMPERATURE
MONITORING
In this example application, an advance warning should be given when the fluid
level reaches 1.18 inch and tank refilling should be started. In addition, the
temperature of the hydraulic fluid should not drop below a minimum value. If,
for example, 68 °F is reached, a stop signal will be given. Furthermore the
temperature, in the form of a 4 .. 20 mA signal, should be made available to a
PLC card.
To achieve this as described in the example, the following settings must be
made in the ENS 3000 menu and the two switching points must be set as
follows:
Menu point Selection Numerical value
Switching output S.S.1 assignment Niv [level]
Switching mode S.m. 1 SP
Switching direction S.d. 1 off
Switch-on delay T
on
1 0
Switch-off delay T
off
1 0
Switching output S.S.2 assignment TEMP
Switching mode S.m. 2 SP
Switching direction S.d. 2 on
Switch-on delay T
on
2 0
Switch-off delay T
off
2 0
Analogue output S.ouT assignment TEMP
Analogue output ouTP MAMP
Switching point settings Numerical value
Switching output S.P.1 1.2
Hysteresis switching output Hi.1 0.02
Switching output S.P.2 0,81
Hysteresis switching output Hi.2 0.02
17. Note
The information in this brochure relates to the operating conditions and
applications described.
For applications or operating conditions not described, please contact the
relevant technical department.
Subject to technical modifications.